Product

CU/XLPE/IS-OS/SWA/PVC

Description

Cable Construction :

* Conductor Plain Annealed Copper wire class 2 according to IEC 60228
* Insulation Extruded XLPE ( Crosslinked Polyethylene )
* Individual Screen Helically Overlapped Polyester Tape
Tinned Annealed Copper Wire 0.5 mm2 ( 20/0.18 mm )
Helically Overlapped Single coated Aluminium Tape contacted with drain wire
Helically Overlapped Polyester Tape
* Overall Screen Helically Overlapped Polyester Tape
Tinned Annealed Copper Wire 0.5 mm2 ( 20/0.18 mm )
Helically Overlapped Single coated Aluminium Tape contacted with drain wire
Helically Overlapped Polyester Tape
* Inner Sheath Extruded PVC Flame Retardant ( Black )
* Armour Galvanized Steel Wire
* Outer Sheath Extruded PVC Flame Retardant ( Black or requested by customer )
Pair Identification :
* 1 Pair Black and White
* Multi Pair Black and White with numbering
Amount of halogen acid gas Max. 17% ( IEC 60754-1)
Limiting oxigen index ( LOI ) Min 30% ( IEC 60332-3 annex B )
Sunlight resistance UL 1581 section 1200
Oil resistance ICEA S-82-552
Flame Retardant IEC 60332-1
Flame Propagation IEC 60332-3 cat. A, B, C
Nominal Voltage 300 V dan 500 V
Insul Resistance Min. 1000 MOhm/km
Test Voltage 300 V : 1000 V/1 min
500 V : 2000 V/1 min
Screen Resistance Min 1 MOhm/km
Min.Bending Radius 6 x OD ( fixed installation )
Temperature Rating -40° C to 70° C
Symbol  : CU/XLPE/IS-OS/SWA/PVC or P1 T2 IS-OS
Applicable Standard Multipair XLPE Insulated Instrumentation Cable
Flame Retardant, UV Resistant
According to BS EN 50288-7 : 2005
Voltage Designation 300 V & 500 V
P1 T2 IS-OS XLPE Insulated, Individual and Overall Collective Screen, Armoured
Other Specification are available on request
Application Suitable for connecting instrument and control system for analogue or digital signal transmission.These cables shall not be connected directly to mains electricity supply or other low impedance sources and not designed to be used for power supply.Suitable for direct buried applications.